CFM and air changes per hour calculator

Enter a room's size and either an airflow or a target air change rate. The other number, and the working, appear straight away.

Step 1: What do you already know?

Step 2: How big is the space?

sq ft
ft

One room, or the whole house.

Step 3: How much air is moving?

CFM

Fan airflow, ventilator rate, or an air cleaner's CADR.

Step 4: Checking a whole house?

Bedrooms feed the ASHRAE 62.2 check. Skip this for a single room.

Air changes per hour

5 ACH

120 CFM × 60 ÷ 1,440 cu ft

Volume
1,440 cu ft
One air change every
12 min
Min. smoke CADR
120 CFM

If this is the whole house

ASHRAE 62.2 continuous ventilation for 180 sq ft and 3 bedrooms: 36 CFM (1.5 ACH of outdoor air).

Size an ERV or HRV for this home

Reference points for this space

BenchmarkCFM needed
Whole-house ventilation, typical result of ASHRAE 62.2roughly 0.3 to 0.4 ACH of outdoor air9
Portable air cleaner sized by the AHAM 2/3 ruleabout 4.8 ACH of filtered air at 8 ft ceilings116
CDC suggestion for occupied spaces5 or more ACH of clean air120

Air changes per hour

5 ACH

See breakdown

The two formulas

ACH = CFM × 60 ÷ volume

CFM = ACH × volume ÷ 60

CFM is cubic feet per minute of airflow. Volume is floor area multiplied by ceiling height, in cubic feet. ACH is how many times per hour a volume of air equal to the room passes through the fan, filter or ventilator.

One air change does not replace every molecule of air in the room, because new air mixes with old. With good mixing, one air change removes about 63% of an airborne contaminant, two remove about 86%, and three about 95%.

Which air are you counting?

  • Outdoor air from an ERV, HRV or exhaust fan dilutes CO₂, moisture and odours. Whole-house rates are low, usually under 0.5 ACH.
  • Filtered air from a portable cleaner or a central system with a good filter removes particles. Use the cleaner's CADR, or the system airflow multiplied by filter efficiency.
  • Recirculated air through a low-grade filter moves air around without cleaning it much. It counts for little.

Use it with the other tools

To size a ventilator for a whole house with the ASHRAE 62.2 formula and see equipment options, use the whole-house filtration and ERV/HRV sizing tool.

Link to this calculator

This page is free to use and to link to. If you cite it, the formulas above are the whole method; there is nothing hidden.

Common questions

How do I calculate air changes per hour?

Multiply the airflow in CFM by 60 to get cubic feet per hour, then divide by the room volume in cubic feet. ACH = CFM × 60 ÷ (floor area × ceiling height).

How do I calculate the CFM needed for a target ACH?

Multiply the target ACH by the room volume and divide by 60. CFM = ACH × volume ÷ 60. A 180 sq ft room with 8 ft ceilings needs 120 CFM for 5 air changes per hour.

What is a good ACH for a house?

It depends which air you are counting. For outdoor-air ventilation of a whole house, ASHRAE 62.2 usually works out to roughly 0.3 to 0.4 ACH. For filtered air in a single room, portable air cleaners sized by the AHAM guideline deliver close to 5 ACH, and CDC guidance suggests aiming for 5 or more air changes per hour of clean air in occupied spaces.

Is CADR the same as CFM?

CADR is measured in CFM, but it is the airflow of fully cleaned air: fan airflow multiplied by the filter's capture efficiency for a given particle type. A cleaner moving 200 CFM through a filter that captures 80% of smoke particles has a smoke CADR of about 160. You can enter CADR in the airflow field to get air changes of clean air.

Does ceiling height matter?

Yes. Air changes depend on volume, not floor area. The same fan gives fewer air changes per hour in a room with 10 ft ceilings than in one with 8 ft ceilings.